PT-Link II Interface
PT-Link II LON
®
Technical Guide
21
VCB-X Data Array
Table 2: VCB-X Modular Data Array For Field Server
Revised 7/8/14
VCB-X Modular Data Array For Field Server
Offset 0 1 2 3 4567
0
AppVer ClSt HtSt SpcTp SaTp OaTp UnitMode CtrlSts
8
ClEnbl HtEnbl EcoEnbl FanDly OnRlys EcoPos VfdBwPos AlmSts
16
AlmGrp1 AlmGrp2 AlmGrp3 SaTpAlm OaTpAlm SpcTpAlm MchClAlm MchHtAlm
24
PofAlm DrtFlAlm SmokeAlm LoSaAlm HiSaAlm CtrlTpCF CtrlTpHF CtrlTp
32
InRh InRhStM MdClPos MdHtPos OcpClSt OcpHtSt UnClOst UnHtOst
40
SaClSt SaHtSt SpcTpOst SaTpOst OaTpOst SchdFrc OnRly1 OnRly2
48
OnRly3 OnRly4 OnRly5 OnRly6 MnExRly1 MnExRly2 MnExRly3 MnExRly4
56
MnExRly5 RlExRly1 RlExRly2 RlExRly3 RlExRly4 RlExRly5 RlExRly6 RlExRly7
64
RlExRly8 RlExRly9 RlExRly10 RlExRly11 RlExRly12 MinEcoSt OaCFM EtCFM
72
SaCFM FrcHvacM FrcFanSp FrcEcono SaTpStM RaTp OaRh StaticPr
80
CO2 BuildPr EtFnSpd CoilTp RaCFM HeadPr RtVlvPos LvWtrTp
88
MdGsVPos HeadPrSt CdCtrSg1 OaClSt OaHtSt WmupTg RhDewpSt EcoEnbSt
96
RaTpOst ColTpOft LWAmbnt PreHtAmb C02MinLv C02MaxLv InRhSt StatPrSt
104
RfPrSt OACfmMin HiInRh ClHdPrSt HtHdPrSt LoClTpSt HiClTpSt SaClRt
112
SaHtRt ClLoRt ClHiRt HtLoRt HtHiRt CtrlMod DschgTp OaWtbl
120
OaDewPt SucPr CoilTpSt RetBydmp RaDmp RaRH SldAdOfs MdSelDb
128
ClStgWdw HtStgWdw MchClLkt MchHtLkt LoSaCf HiSaCf DfrSt LvH2OOst
136
CO2Ost CTpHiAlm CTpLoAlm HpLkt VFDClMin VFDHtMin VFDVtMin MaxEcoHt
144
MaxEcoCO HpDfrInt AptDfr DuctPfDb RlfPrDb OaCfmDb SZVAVFnI SaWmupSt
152
SaCldnSt RehtEnbl EmHtEnbl RaTpAlm MisEM1 ColPfAlm CO2Alm DschgAlm
160
OaCfmAlm ExtCmSr SaCfmSr RaCfmSr MisMHGRV MisMDGAS Mis12Rly HiCtrlMd
168
LoCtrlMd DigCmpCf DigCmpLk HiHedPr H2OProf LoSucPr HiSucPr –
Komentarze do niniejszej Instrukcji