VCM-X Modular E-BUS Controller Technical Guide
APPENDIX
75
OE265-11, -13, and -14 RH Sensors
OE265-11, OE265-13, OE265-14 Relative Humidity
Sensor Testing Instructions
Use the voltage column to check the Humidity Sensor while connected
to a powered expansion module. Read voltage with meter set on DC
volts.
Place the “-” (minus) lead on the terminal labeled GND and the “+”
lead on the AIN terminal that the Humidity sensor is connected to on
the Analog Input/Output Expansion Module.
OE265 Series RH Sensor Testing
The chart below is used to troubleshoot the OE265-11, OE265-13, and
OE265-14 Relative Humidity Sensors.
OE265-11, -13 & -14 Relative Humidity
Transmitters –
Humidity vs. Voltage for 0-5 VDC Sensors
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
0% 0.00 52% 2.60
2% 0.10 54% 2.70
4% 0.20 56% 2.80
6% 0.30 58% 2.90
8% 0.40 60% 3.00
10% 0.50 62% 3.10
12% 0.60 64% 3.20
14% 0.70 66% 3.30
16% 0.80 68% 3.40
18% 0.90 70% 3.50
20% 1.00 72% 3.60
22% 1.10 74% 3.70
24% 1.20 76% 3.80
26% 1.30 78% 3.90
28% 1.40 80% 4.00
30% 1.50 82% 4.10
32% 1.60 84% 4.20
34% 1.70 86% 4.30
36% 1.80 88% 4.40
38% 1.90 90% 4.50
40% 2.00 92% 4.60
42% 2.10 94% 4.70
44% 2.20 96% 4.80
46% 2.30 98% 4.90
48% 2.40 100% 5.00
50% 2.50
Table 5: Humidity/Voltage for OE265-11, -13 & -14
Humidity Sensors