Zone
Zone
INSTALLATION AND WIRING
RNE Modular Controller Field Technical Guide
24
Figure 14: Economizer Damper Actuator Wiring
24 VAC Power Source
Sized For Actuator VA Load
24 VAC
GND
2-10 VDC
Output
RNE Controller
GND
AO1
AI1
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Economizer Damper Actuator
(Belimo Actuator Shown)
Y1 3
+ 2
COM - 1
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturer Wiring
Instructions
Economizer Feedback 5
NOTE: For Economizer
Actuator Feedback Signal,
See Wiring For The
VCM-X Expansion Module.
AI3
Economizer Damper Actuator
The Economizer Damper Actuator signal voltage output is a 2-10 VDC
output. This signal output is used by the RNE Controller to modulate
the Economizer Damper Actuator in order to control the amount of
Outdoor Air delivered to the HVAC unit for Free Cooling and/or Indoor
Air Quality requirements. See Figure 14 for detailed wiring.
WARNING: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe
the correct polarity will result in damage to the actuator or RNE
Controller.
Economizer Damper Actuator Wiring
Komentarze do niniejszej Instrukcji