RNE Modular Controller Field Technical Guide
4
Features
The RNE Modular Controller (OE332-23E-RNE-A) is designed with 7
analog inputs, 2 analog outputs, and 5 relay outputs. Each RNE Control-
lers input and output capabilities can be expanded with the VCM-X
Expansion Module (OE333-23-EM), the 12 Relay Expansion Module
(OE358-23-12R), and the 4 Binary Input Expansion Module (OE356-
01-BI) by means of a modular cable.
The RNE Controller also allows various E-BUS modules to connect
directly to it. These would include the Full Digital Module, the Two
Condenser Head Pressure Module, and the Water Source Heat Pump
Modules.
Each RNE Controller can be con gured for control of VAV Units (with
or without VAV/Zone Controllers), Constant Volume Units, and Make-
Up Air Units. Features include the following:
Up to a Combined Total of 20 Stages of Heating & Cooling
Modulating Cooling Outputs (VFD Compressor or Chilled
Water Valve Control)
Modulating Heating Output ( Hot Water Valve,
Steam Valve, SCR Electric Heat Control)
Full Integration with the AAON
®
MODGAS-X Modulating
Natural Gas Controller
Full Integration with the AAON
®
MHGRV-X Modulating
Hot Gas Reheat Controller
Con gurable for Heat Pump Applications
Advanced Dehumidi cation Capabilities
Air Flow Monitoring of Outdoor Air, Supply Air,
and Return Air Streams
Air Flow Control of Outdoor Air Damper
Single Zone VAV Control
Primary/Secondary Heating Control
Adaptive Supply Air Reset
Selectable Control Sensor
Fan Proving Interlock
Features and Applications
Dirty Filter Alarm
Emergency Shutdown Input (Smoke Detector/Firestat or
other Shutdown Conditions)
Drybulb/Wetbulb Control of Economizer Operation
Building Pressure Control
Remote Override Capabilities
IAQ Economizer Reset
Title 24 Economizer Certi ed
7-Day, 2-Event-per-Day Scheduling
14 Holiday Event Scheduling
Optimal Start Scheduling
Trend Logging Capability
Static Pressure Control for Filter Loading Applications
Accepts Remote HVAC Mode Selection Via Contact
Closure On VCM-X Expansion Module
Con gurable for AAON
®
PAC and DPAC Applications
Heat Wheel - On/Off Control
Con gurable for R22 and R410-A refrigerant
Head Pressure Control
Full Digital Control
Water Source Heat Pump Monitoring
Most common HVAC unit control applications can be con gured using
only the RNE Controller. If the application requires more inputs and/
or outputs, optional expansion modules are available to provide for ad-
ditional analog, binary, or digital inputs and outputs as required.
The available expansion module con gurations allow for 4 or 8 addition-
al binary inputs, 4 additional analog inputs, 5 additional analog outputs,
and up to 16 additional binary (relay) outputs. The various expansion
modules plug into the RNE Controller by means of a modular cable.