APPENDIX D - VCC-X BACnet
®
VCC-X Controller Technical Guide
104
VCC-X BACnet
®
Parameters
BACnet
®
Properties for the VCC-X Controller
Parameter Object Description
Limits
Bad or
Missing
Module #1
BI:38 Refrigeration Module #1 is
bad or missing.
Bad or
Missing
Module #2
BI:39 Refrigeration Module #2 is
bad or missing.
Bad or
Missing
Module #3
BI:40 Refrigeration Module #3 is
bad or missing.
Bad or
Missing
Module #4
BI:41 Refrigeration Module #4 is
bad or missing.
Bad or
Missing
Preheat
Module
BI:42 Preheater Module is bad or
missing.
Bad or
Missing
Reheat Board
BI: 43 The MHGR board is
confi gured but not detected.
Bad or
Missing
MODGAS
Board
BI: 44 The MODGAS board is
confi gured but not detected.
Bad or Miss-
ing EM1
Module
BI:45 EM1 Expansion Board is
bad or missing.
Bad or
Missing 12
Relay
Expansion
Board.
BI: 46 The 12 Relay Expansion
Board is confi gured but not
detected.
Compressor
A1 Safety
BI:47 Compressor A1 Not
Running. This RSM alarm
occurs when a compressor
relay is on, but there is not
24VAC at the Comp Status
input for the compressor.
Compressor
A2 Safety
BI:48 Compressor A2 Not
Running. This RSM alarm
occurs when a compressor
relay is on, but there is not
24VAC at the Comp Status
input for the compressor.
Outside Coil
'A' Temp
Switch
BI:49 Outside Coil 'A' Temp
Switch for Defrost Mode
Module #1
Binary Input
#4
BI:50 Future use for Binary Input
#4
BACnet
®
Properties for the VCC-X Controller
Parameter Object Description
Limits
Compressor
B1 Alarm
BI:51 Compressor B1 Not
Running. This RSM alarm
occurs when a compressor
relay is on, but there is not
24VAC at the Comp Status
input for the compressor.
Compressor
B2 Alarm
BI:52 Compressor B2 Not
Running. This RSM alarm
occurs when a compressor
relay is on, but there is not
24VAC at the Comp Status
input for the compressor.
Outside Coil
'B' Temp
Switch
BI:53 Outside Coil 'B' Temp Switch
for Defrost Mode
Module #2
Binary Input
#4
BI:54 Future use for Binary Input
#4
Compressor
C1 Alarm
BI:55 Compressor C1 High
Pressure Alarm. Stops
Compressor.
Compressor
C2 Alarm
BI:56 Compressor C2 High
Pressure Alarm. Stops
Compressor.
Outside Coil
'C' Temp
Switch
BI:57 Outside Coil 'C' Temp
Switch for Defrost Mode
Module #3
Binary Input
#4
BI:58 Future use for Binary Input
#4
Compressor
D1 Alarm
BI:59 Compressor D1 High
Pressure Alarm. Stops
Compressor.