Orion-system VCC-X Controller Instrukcja Użytkownika Strona 92

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 91
APPENDIX C - RSMV LCD SCREENS
VCC-X Controller Technical Guide
92
CONFIG
VFD TEST
ADDRESS
1(152)
REFRIG
MODULE
E-BUS
+0
SOFTWARE
1072v101
Hold for 5 seconds.
DIAGNSTC
ENTER TO
EXIT
Protected Screens Map
Refer to the following map when navigating through the LCD
Protected Screens. From the REFRIG MODULE Screen, press
<ENTER> twice to get to the Software Screen. Then hold the <UP>
button for 5 seconds. To scroll through the rest of the screens, press
the <MENU> button.
Alarm History & Protected Screens
Alarm History Screens
The ALARM HISTORY Screen displays past alarms, if any, and how
long ago the last of each type occurred. From the ALARM HISTORY
Screen, press <ENTER> to scroll through the history screens.
ALARM
HISTORY
The Alarm will appear on the rst line and the second line will display
how long ago each alarm last occurred. As a result, the alarms listed
on the ALARMS screen will be abbreviated as follows in order of
the way they are listed in the prior ALARMS screen section.
LOW SPLow Suction Pressure
UNSAFE SPUnsafe Suction Pressure
SP SENSENo Suction Pressure Sensor Detected
HIGH HPHigh Head Pressure
HP SENSENo Head Pressure Sensor Detected
CL TEMP 1Coil Temp 1 Failure
CL TEMP 2Coil Temp 2 Failure
COMP 1 FLCompressor 1 Failure
COMP 2 FLCompressor 2 Failure
LOW SH1Low Superheat 1
LOW SH2Low Superheat 2
COMM T/0E-BUS Slave Timeout
NOTE: The screen will display minutes for the rst 60 minutes
of alarm occurrence, hours for the next 72 hours of
alarm occurrence, and days for the next 30 days of
alarm occurrence. After 30 days, the alarm will clear.
Alarm history is not stored in memory. So, if power
is lost, the alarms will clear.
EBUS SLAVE (SLV) TIMEOUT: This alarm indicates that com-
munication has been lost between the RSMV and the Main controller
or other E-BUS modules that may be connected. This can be the result
of a bad cable, a missing cable, or the module not being con gured
properly.
Przeglądanie stron 91
1 2 ... 87 88 89 90 91 92 93 94 95 96 97 ... 119 120

Komentarze do niniejszej Instrukcji

Brak uwag